Conduit Fill Calculator (NEC)

Calculate NEC Chapter 9 conduit fill for EMT, PVC and rigid conduit with THHN, XHHW and THW conductors, and find the smallest conduit size that fits.

InsulationSizeQtyArea each
0.0133 in²
0.0133 in²
Conductors4 (total area 0.0532 in² / 34.3 mm²)
Maximum fill (NEC Ch. 9 Table 1)40 %
Smallest EMT1/2 in.
Trade sizeInternal areaFill
1/2 in.0.304 in²17.5 %✓
3/4 in.0.533 in²10.0 %✓
1 in.0.864 in²6.2 %✓
1-1/4 in.1.496 in²3.6 %✓
1-1/2 in.2.036 in²2.6 %✓
2 in.3.356 in²1.6 %✓
2-1/2 in.5.858 in²0.9 %✓
3 in.8.846 in²0.6 %✓
3-1/2 in.11.545 in²0.5 %✓
4 in.14.753 in²0.4 %✓

Areas from NEC Chapter 9 Tables 4 and 5. Fill limits: 53 % for one conductor, 31 % for two, 40 % for three or more. Nipples under 24 in. may be filled to 60 %. Always confirm against the code edition adopted in your area.

About this conduit fill calculator

Check conduit fill to NEC Chapter 9 for EMT, PVC Schedule 40 and rigid metal conduit. Mix conductor types and sizes, see the fill percentage for every trade size from 1/2 in. to 4 in., and find the smallest conduit that meets the 53 %, 31 % or 40 % limit.

How to use the Conduit Fill Calculator (NEC)

  1. Choose the conduit type.
  2. Add conductors with insulation, size and quantity.
  3. Read the fill percentage and smallest allowed trade size.

Example

3 × 12 AWG THHN + 1 × 12 AWG ground in EMT  →  1/2 in. (17.5 %)

Frequently asked questions

What is the maximum conduit fill?

40 % for three or more conductors, 31 % for two and 53 % for one (NEC Chapter 9, Table 1).

Does the ground wire count?

Yes. Equipment grounding conductors are included when calculating fill.