About this cable size and voltage drop calculator (IEC 60364 / NEC)
Size electrical cables for single-phase, three-phase and DC circuits using IEC 60364-5-52 metric sizes or NEC Table 310.16 AWG and kcmil sizes. The calculator checks current-carrying capacity with a derating factor and voltage drop, and recommends the smallest conductor that satisfies both.
How to use the Cable Size Calculator (mm² & AWG) – IEC & NEC
- Pick IEC or NEC, the system type, conductor and insulation.
- Enter voltage, load current or power, cable length and maximum voltage drop.
- Read the recommended cable size, voltage drop and power loss.
Example
400 V 3-phase, 32 A, 50 m, Cu PVC → 6 mm² (≈ 2.1 % drop)
Frequently asked questions
What voltage drop is acceptable?
IEC 60364-5-52 suggests 3 % for lighting and 5 % for other uses on public supplies; NEC informational notes recommend 3 % on branch circuits and 5 % overall.
What is the derating factor?
The product of correction factors for ambient temperature and grouping of circuits. Use 1.0 for a single circuit at 30 °C.
Worked example: cable size for 32 A over 50 m at 400 V three-phase?
A 6 mm² copper PVC cable carries the current and gives about 2.1 % voltage drop (ΔV = √3 × I × L × (R cosφ + X sinφ)). The NEC equivalent is roughly 8 AWG at 75 °C.
Can I use AWG instead of mm²?
Yes. Switch the standard to NEC to size in AWG and kcmil using Table 310.16, or IEC to size in mm² using IEC 60364-5-52.