Cable Size Calculator (mm² & AWG) – IEC & NEC

Size cables by ampacity and voltage drop using IEC 60364 (mm²) or NEC 310.16 (AWG/kcmil).

Design current32 A
Minimum size by ampacity4 mm²
Minimum size by voltage drop6 mm²
Recommended size6 mm²
Voltage drop8.22 V (2.05 %)
Voltage at load391.78 V
Power loss528.1 W
SizeAmpacity (A)Drop (%)
1.5 mm² 17.5 8.13 ampacity
2.5 mm² 24 4.89 ampacity
4 mm² 32 3.07 drop
6 mm² 41 2.05 ✓
10 mm² 57 1.24 ✓
16 mm² 76 0.79 ✓
25 mm² 96 0.52 ✓
35 mm² 119 0.38 ✓
50 mm² 144 0.27 ✓
70 mm² 184 0.2 ✓
95 mm² 223 0.16 ✓
120 mm² 259 0.13 ✓
150 mm² 299 0.11 ✓
185 mm² 341 0.09 ✓
240 mm² 403 0.08 ✓
300 mm² 464 0.07 ✓

Ampacity: IEC 60364-5-52 Table B.52.4/B.52.5, installation method C (clipped direct), three loaded conductors, 30 °C ambient. Aluminium values are approximate (≈78% of copper). Voltage drop uses conductor resistance at the insulation's rated temperature and 0.08 mΩ/m reactance. Results are estimates; always verify against your local code and manufacturer data.

About this cable size and voltage drop calculator (IEC 60364 / NEC)

Size electrical cables for single-phase, three-phase and DC circuits using IEC 60364-5-52 metric sizes or NEC Table 310.16 AWG and kcmil sizes. The calculator checks current-carrying capacity with a derating factor and voltage drop, and recommends the smallest conductor that satisfies both.

How to use the Cable Size Calculator (mm² & AWG) – IEC & NEC

  1. Pick IEC or NEC, the system type, conductor and insulation.
  2. Enter voltage, load current or power, cable length and maximum voltage drop.
  3. Read the recommended cable size, voltage drop and power loss.

Example

400 V 3-phase, 32 A, 50 m, Cu PVC  →  6 mm² (≈ 2.1 % drop)

Frequently asked questions

What voltage drop is acceptable?

IEC 60364-5-52 suggests 3 % for lighting and 5 % for other uses on public supplies; NEC informational notes recommend 3 % on branch circuits and 5 % overall.

What is the derating factor?

The product of correction factors for ambient temperature and grouping of circuits. Use 1.0 for a single circuit at 30 °C.

Worked example: cable size for 32 A over 50 m at 400 V three-phase?

A 6 mm² copper PVC cable carries the current and gives about 2.1 % voltage drop (ΔV = √3 × I × L × (R cosφ + X sinφ)). The NEC equivalent is roughly 8 AWG at 75 °C.

Can I use AWG instead of mm²?

Yes. Switch the standard to NEC to size in AWG and kcmil using Table 310.16, or IEC to size in mm² using IEC 60364-5-52.