Wire Resistance Calculator (mm² & AWG)

Calculate the resistance of copper, aluminium and other wires from length, cross-section (mm² or AWG) and temperature, with voltage drop and power loss.

Cross-section (mm²)
Wire length (m)
Temperature (°C)
Current (A, optional)
Round trip (×2 length)
Resistance689.6 mΩ
Per km / per 1000 ft6.896 Ω/km · 2.102 Ω/1000 ft
Cross-section2.5 mm² (Ø 1.78 mm)
Resistivity at 20 °C1.724E-08 Ω·m

R = ρ × L / A, with ρ(T) = ρ₂₀ × (1 + α(T − 20)). DC resistance; AC skin effect is ignored.

About this wire resistance calculator

Calculate the DC resistance of copper, aluminium, silver, gold, steel or nichrome wire from its length, cross-section (mm², AWG or diameter) and temperature. Optionally enter a current to see the voltage drop and power loss.

How to use the Wire Resistance Calculator (mm² & AWG)

  1. Choose the material and how to specify the size.
  2. Enter the length and temperature.
  3. Read the resistance, Ω/km and losses.

Example

100 m of 2.5 mm² copper at 20 °C  →  0.69 Ω

Frequently asked questions

How much does temperature change resistance?

Copper resistance rises by about 0.39 % per °C, so a conductor at 70 °C has about 20 % more resistance than at 20 °C.

What is the resistivity of copper?

About 1.72 × 10⁻⁸ Ω·m (0.0172 Ω·mm²/m) at 20 °C for annealed copper.