About this voltage drop calculator (mm² and AWG)
Calculate the voltage drop along a cable for DC, single-phase and three-phase circuits. Choose metric sizes in mm² (IEC) or AWG/kcmil (NEC), copper or aluminium conductors, and include power factor, reactance, conductor temperature and parallel runs. The calculator also suggests the smallest cable that stays within your allowed percentage drop.
How to use the Voltage Drop Calculator (mm² & AWG)
- Choose the system, conductor material and size standard.
- Enter voltage, load current, one-way length and the cable size.
- Read the drop in volts and percent and the recommended size.
Example
230 V, 16 A, 30 m of 2.5 mm² copper, single-phase → ≈ 7.2 V (3.1 %)
Frequently asked questions
What is an acceptable voltage drop?
IEC 60364 recommends 3 % for lighting and 5 % for other loads from the origin; the NEC informational notes suggest 3 % for a branch circuit and 5 % total.
Should I enter one-way or round-trip length?
One-way. The formula already accounts for the return conductor (×2 for single-phase and DC, ×√3 for three-phase).
Why does aluminium need a larger cable?
Aluminium has about 64 % higher resistivity than copper, so it needs roughly 1.6 times the cross-section for the same voltage drop.
Is my data safe?
Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.
Is it free?
Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.