Ampacity Table & Calculator

NEC Table 310.16 conductor ampacity for copper and aluminum at 60/75/90 °C, with ambient temperature and conductor bundling corrections.

Temperature correction: 60 °C ×1.00, 75 °C ×1.00, 90 °C ×1.00. Bundling adjustment (3 conductors): ×1.00.
Sizemm² 60 °C75 °C90 °C 60 °C corrected75 °C corrected90 °C corrected
14 AWG 2.08 152025 15 20 25
12 AWG 3.31 202530 20 25 30
10 AWG 5.26 303540 30 35 40
8 AWG 8.37 405055 40 50 55
6 AWG 13.3 556575 55 65 75
4 AWG 21.15 708595 70 85 95
3 AWG 26.67 85100115 85 100 115
2 AWG 33.63 95115130 95 115 130
1 AWG 42.41 110130145 110 130 145
1/0 AWG 53.48 125150170 125 150 170
2/0 AWG 67.43 145175195 145 175 195
3/0 AWG 85.03 165200225 165 200 225
4/0 AWG 107.22 195230260 195 230 260
250 kcmil 126.68 215255290 215 255 290
300 kcmil 152.01 240285320 240 285 320
350 kcmil 177.35 260310350 260 310 350
400 kcmil 202.68 280335380 280 335 380
500 kcmil 253.35 320380430 320 380 430
600 kcmil 304.02 350420475 350 420 475
750 kcmil 380.03 400475535 400 475 535
1000 kcmil 506.71 455545615 455 545 615

Based on NEC Table 310.16: not more than three current-carrying conductors in a raceway, cable or earth, 30 °C ambient. Small conductors are also limited by NEC 240.4(D) overcurrent protection (Cu: 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A; Al: 12 AWG 15 A, 10 AWG 25 A), and terminations are usually rated 60 °C (≤ 100 A) or 75 °C. Always verify against the code edition adopted locally.

About this wire ampacity table and calculator

Look up the allowable ampacity of copper and aluminum conductors from NEC Table 310.16 at 60, 75 and 90 °C, and apply the ambient temperature correction and the adjustment for more than three current-carrying conductors. Enter a load current to find the smallest suitable wire size.

How to use the Ampacity Table & Calculator

  1. Choose copper or aluminum.
  2. Enter the ambient temperature and number of current-carrying conductors.
  3. Enter the load to highlight the smallest conductor.

Example

12 AWG Cu, 75 °C, 40 °C ambient  →  25 A × 0.88 = 22 A

Frequently asked questions

Why can 12 AWG only be protected at 20 A?

NEC 240.4(D) limits overcurrent protection for small conductors regardless of the table ampacity: 14 AWG Cu 15 A, 12 AWG Cu 20 A, 10 AWG Cu 30 A.

Which temperature column should I use?

Usually the lowest temperature rating of the conductor, terminals and connected devices; 60 °C for circuits up to 100 A unless equipment is marked 75 °C.

Is my data safe?

Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.

Is it free?

Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.