Circuit Breaker & Fuse Size Calculator (NEC & IEC)

Find the right circuit breaker or fuse rating for a load using NEC (continuous 125 %, motor 250 %) or IEC MCB ratings for single-phase, three-phase and DC circuits.

Load current (A)
Load current24.00 A
Sizing factor125 %
Minimum rating30.00 A
Recommended breaker / fuse30 A

NEC 210.20(A): overcurrent devices for continuous loads are sized at 125 % of the load. The conductor must also be rated for the circuit; see the ampacity table and cable size calculator.

About this circuit breaker size calculator

Work out the breaker or fuse rating for a load. Continuous loads are sized at 125 %, motor branch circuits up to 250 % for inverse-time breakers or 175 % for time-delay fuses, and the result is rounded up to the next NEC 240.6 or IEC standard rating.

How to use the Circuit Breaker & Fuse Size Calculator (NEC & IEC)

  1. Choose NEC or IEC ratings and the system.
  2. Pick the load type and enter current or power.
  3. Read the minimum and recommended rating.

Example

24 A continuous load (NEC)  →  30 A breaker

Frequently asked questions

Why 125 % for continuous loads?

Standard breakers are only rated to carry 80 % of their rating continuously, so the load is multiplied by 1.25 (NEC 210.20).

Does the wire size have to match?

Yes. The conductor ampacity must be protected by the breaker; check it with the ampacity table.

Is my data safe?

Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.

Is it free?

Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.