About this motor full load current calculator
Calculate the full-load current of single-phase and three-phase motors from kW or horsepower, voltage, efficiency and power factor. The tool also estimates starting current for direct-on-line, star-delta, soft starter and VFD starting, and suggests overload settings, contactor and breaker sizes.
How to use the Motor Full-Load Current & Starter Size Calculator
- Choose single- or three-phase and kW or hp.
- Enter power, voltage, efficiency and power factor.
- Read the FLC, starting currents and starter sizing.
Example
7.5 kW, 400 V, 3-phase, η 90 %, pf 0.85 → ≈ 14.2 A
Frequently asked questions
How much current does a motor draw when starting?
Typically 6 to 8 times full-load current direct-on-line, about a third of that with star-delta.
Should I use nameplate or table current?
For NEC conductor and branch-circuit protection sizing use the table values (430.247–430.250); use nameplate current for overload settings.