About this power factor correction capacitor calculator (kVAR and µF)
Calculate the capacitor bank size needed to raise power factor for single-phase and three-phase loads. Enter the real power in kW, the existing power factor from your bill or meter and the target (typically 0.95 to 0.98) to get the required kVAR, the capacitance per phase in microfarads for star (wye) and delta connection, and the resulting reduction in line current, apparent power (kVA) and I²R losses. The formula used is Qc = P × (tan φ₁ − tan φ₂), where φ = arccos(PF).
How to use the Power Factor Correction Calculator
- Choose single-phase or three-phase, the line voltage and the frequency (50 or 60 Hz).
- Enter the load in kW (or kVA and PF) and the existing and target power factor.
- Read the required kVAR, the capacitor value in µF per phase and the new current.
Example
100 kW, 400 V 3-ph, PF 0.75 → 0.95 → Qc = 100 × (0.882 − 0.329) = 55.3 kVAR
→ delta: 367 µF per phase, line current 192 A → 152 A (−21 %)Frequently asked questions
Why correct power factor?
A higher power factor lowers the current drawn for the same real power, which reduces cable losses and voltage drop, frees transformer and switchgear capacity, and avoids the reactive-power or low-PF penalty charges that many utilities add to commercial bills.
What is the power factor correction formula?
Required reactive power Qc (kVAR) = P (kW) × (tan φ₁ − tan φ₂), where φ₁ = arccos(existing PF) and φ₂ = arccos(target PF). Capacitance per phase: C = Qc / (2π f V²) for single-phase, and for three-phase C = Qc / (3 × 2π f V²) with V = line voltage in delta or phase voltage in star.
How many kVAR do I need per kW?
It depends only on the starting and target PF. Rough multipliers per kW: from 0.70 to 0.95 use 0.69 kVAR; 0.75 → 0.95 use 0.55; 0.80 → 0.95 use 0.42; 0.85 → 0.95 use 0.29; 0.90 → 0.95 use 0.16. Multiply by the load in kW.
Should I correct to unity (1.0) power factor?
Usually not. Most engineers target 0.95 to 0.98. Going to unity risks over-correction (leading PF) when the load drops, which raises voltage and can cause resonance with harmonics. Automatic capacitor banks switch steps in and out to track the load.
What is the difference between star and delta capacitor connection?
In delta each capacitor sees line voltage, so one third of the capacitance is needed compared with star, but the capacitor voltage rating must be higher. Low-voltage banks are usually delta; medium-voltage banks are often star. The tool shows both values.
How do I size a capacitor for a single motor?
Correct to about 0.95 at the motor's rated kW and PF from its nameplate, but never exceed 90 % of the motor's no-load magnetising kVAR, or the motor can self-excite when switched off. Motor manufacturers publish maximum capacitor kVAR tables for this reason.
Does power factor correction reduce my kWh consumption?
Not directly. Real energy (kWh) stays the same; what drops is current, kVA demand and the I²R losses in your own cables and transformers (typically 1 to 3 %). The savings come mostly from removed penalty charges and lower demand (kVA) tariffs.
Is my data safe?
Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.
Is it free?
Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.