DevToolsHub Free · Fast · 100% in your browser

Transformer Current & Fault Calculator

Calculate transformer full-load current on both windings and the maximum short-circuit current from impedance (%Z).

PrimarySecondary
Full-load current52.49 A1,443.38 A
Max. short-circuit current0.87 kA24.06 kA
Turns ratio27.5 : 1
Short-circuit power16.67 MVA

Isc = IFL × 100 / %Z, assuming an infinite source (upstream impedance ignored). The actual fault current will be lower.

About this transformer fault current calculator (kVA and %Z)

Calculate the rated full-load current of single-phase and three-phase transformers on both the primary and secondary windings, and the maximum short-circuit (fault) current available at the secondary terminals from the nameplate percentage impedance (%Z). The full-load amps tell you how to size the transformer's cables, breakers and fuses; the fault current tells you the minimum interrupting rating (kA) the downstream switchgear must have. Formulas: I = kVA × 1000 / (√3 × V) for three-phase, I = kVA × 1000 / V for single-phase, and I_sc = I_FL × 100 / %Z.

How to use the Transformer Current & Fault Calculator

  1. Enter the kVA rating and the nameplate impedance %Z (typically 2 to 8 %).
  2. Enter the primary and secondary line voltages and choose single- or three-phase.
  3. Read the full-load current on each side and the maximum secondary fault current in kA.

Example

1000 kVA, 11 kV / 400 V, 6 %Z, 3-ph  →  primary 52.5 A, secondary 1443 A, fault 24.1 kA
75 kVA, 480 V / 208 V, 3 %Z, 3-ph     →  primary 90 A, secondary 208 A, fault 6.9 kA
25 kVA, 240 V / 120 V, 2.5 %Z, 1-ph   →  primary 104 A, secondary 208 A, fault 8.3 kA

Frequently asked questions

How do I calculate transformer full-load current?

Three-phase: I = kVA × 1000 ÷ (1.732 × line voltage). Single-phase: I = kVA × 1000 ÷ voltage. A 500 kVA 400 V three-phase transformer therefore delivers 500 000 ÷ (1.732 × 400) = 722 A at full load.

How do I calculate transformer short-circuit current?

Divide the full-load current by the per-unit impedance: I_sc = I_FL × 100 ÷ %Z. A 1000 kVA 400 V transformer (1443 A) with 6 %Z gives 1443 × 100 ÷ 6 ≈ 24 kA. This is the infinite-bus value used to specify breaker interrupting ratings.

Why is the real fault current lower?

The calculation assumes an infinite upstream source. Utility source impedance, upstream transformers and cable impedance all add to the loop and reduce the actual fault current, often by 10 to 30 %. For protection coordination, use the calculated value as a conservative maximum.

What is %Z (percent impedance) on a transformer?

The percentage of rated primary voltage needed to circulate rated current with the secondary short-circuited. It is printed on the nameplate and is typically 2 to 3 % for small dry-type units, 4 to 6 % for distribution transformers and 6 to 10 % for large power transformers. Lower %Z means better voltage regulation but higher fault current.

How do I size the breaker or fuse for a transformer?

Under NEC 450.3 the primary overcurrent device is typically up to 125 % of primary full-load current (250 % with secondary protection), and the secondary device up to 125 % of secondary full-load current. Use the full-load amps from this calculator with the breaker size calculator to pick a standard rating.

What size cable do I need for a transformer secondary?

Size the secondary conductors for at least 125 % of the secondary full-load current (NEC 215.2 / 450) and check voltage drop over the run. Take the secondary amps from here into the cable size calculator.

How do I convert kVA to amps for a transformer?

Use the same formulas: amps = kVA × 1000 ÷ (1.732 × V) for three-phase or kVA × 1000 ÷ V for single-phase. Common 400 V three-phase values: 100 kVA = 144 A, 250 kVA = 361 A, 500 kVA = 722 A, 1000 kVA = 1443 A, 1600 kVA = 2309 A, 2500 kVA = 3608 A.

Is my data safe?

Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.

Is it free?

Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.