About this short-circuit current and cable withstand calculator
Estimate the prospective short-circuit current at a transformer's terminals and at the end of a cable, and check whether the cable can withstand the fault until the protective device clears it. Uses the transformer impedance method and the adiabatic equation k²S² ≥ I²t from IEC 60364 and BS 7671 for PVC and XLPE cables.
How to use the Short-Circuit Current & HV/LV Cable Withstand Calculator
- Enter transformer kVA, %Z and secondary voltage.
- Choose cable material, insulation, size, length and parallel runs.
- Enter the fault clearing time and read the fault current and withstand.
Example
1000 kVA, 5.75 %, 400 V → ≈ 25 kA at the transformer
Frequently asked questions
What is the k factor?
A constant depending on conductor and insulation: 115 for copper PVC, 143 for copper XLPE, 76 for aluminium PVC and 94 for aluminium XLPE.
Is this suitable for high-voltage cables?
Yes for a first estimate. Use the medium-voltage secondary voltage and short clearing times; for detailed studies include the upstream grid impedance.
Is my data safe?
Yes. The tool runs entirely in your browser using WebAssembly. Nothing you type or upload is sent to a server, logged or stored.
Is it free?
Yes, completely free with no sign-up, no limits and no watermarks. It also works offline once the page has loaded.