DevToolsHub Free · Fast · 100% in your browser

Ground Rod / Earth Electrode Resistance Calculator

Estimate the earth resistance of a single ground rod and of multiple rods in a line from soil resistivity, rod length, diameter and spacing (Dwight / BS 7430 / IEEE 142).

Soil type
Soil resistivity ρ (Ω·m)
Rod length (m)
Rod diameter (mm)
Number of rods (in a line)
Target resistance (Ω)
Single rod resistance40.39 Ω
Result vs target✗ 40.39 Ω > 25 Ω
Rods needed at this spacing2

Single rod (Dwight): R = ρ / (2πL) × (ln(8L/d) − 1). Multiple rods in a line (BS 7430): R = R₁ × (1 + λα) / n, with α = ρ / (2πR₁s). Rods should be spaced at least their own length apart. NEC 250.53(A)(2) requires a supplementary electrode unless a single rod is 25 Ω or less.

About this ground rod resistance calculator

Estimate the resistance to earth of a driven ground rod using Dwight's formula, and of several rods in a line using the BS 7430 method. See how soil resistivity, rod length, diameter and spacing affect the result and how many rods are needed to meet a target such as 25 Ω.

How to use the Ground Rod / Earth Electrode Resistance Calculator

  1. Choose a soil type or enter measured resistivity.
  2. Enter rod length, diameter, number and spacing.
  3. Read the earth resistance and rods needed.

Example

100 Ω·m soil, 2.4 m × 16 mm rod  →  ≈ 40 Ω

Frequently asked questions

What earth resistance is required?

NEC 250.53 requires an additional electrode unless one rod is 25 Ω or less; many utilities and data centres target 5 Ω or less.

How far apart should ground rods be?

At least the length of the rod, and ideally twice the length, otherwise their resistance areas overlap.